Blog

Cloudy Exit Requirements

If you enjoyed this post, we encourage you to share!

There is a lack of clarity surrounding exits in the Building Code…and it has me fired up. I may sound like a broken record, but exits are sacred and I feel very strongly about them.

The exit is one of the most important passive fire protection elements in a building, and is fundamental in the event of an emergency. It is a building occupants’ life-line out of a building, as well as safe access into the building for emergency responders.

The purpose of this post is to summarize my thoughts around some of the requirements of exits that I have found to be interpreted and applied differently across the country.

I challenge you to review the Code requirements closely, turn off auto-pilot, put on your thinking cap, and see what you think is the most appropriate. And just a friendly reminder that status quo does not equal correct.

I’ve written a previous post on exits you can also refer to (Guide to Exits – Part 1), and Lara has discussed exits as well in her post Egress vs Exit?.

Let’s dive in!


Fire-Resistance Rating of Exit Separations (3.4.4.1.)

I once went down a rabbit hole of the required rating of exit fire separations…what I found is a bit of discrepancy between Part 9 and Part 3. Let me explain:

The common and accepted application is that the exit separation is based solely on the 3.2.2. requirement and does not consider higher ratings required by major occupancy or storage/repair garages. This is stated in Sentence 3.4.4.1.(1):

I do agree the Code is pretty clear in Part 3 that only 3.2.2. is to be applied (although I don’t necessarily agree that this is right), however Clause 9.9.4.2.(1)(a) does not reference Table 9.10.8. for protection of structural members (however, Clause 9.9.4.2.(1)(b) does.). Table 9.10.8. gives us some of the information that we would fine in the 3.2.2. classification if the building was Part 3.  This is stated in Sentence 9.9.4.2.(1):

Now for an example, which highlights the discrepancy:

  1. A Part 9, 599 m2 two storey building. First storey commercial repair garage (F2) and second storey is one (giant) residential suite (C). Floor is required 2 h per Article 9.10.9.17. Per 9.9.4.2., the exit at the first storey is required to be 2 h, but 45 min at the second level.
  2. A Part 3, 602 m2 two storey building (3.2.2.76.). First storey commercial repair garage (F2) and second storey in one (giant) residential suite (C). Floor is required 2 h per 3.3.5.6., but exit at first storey only 45 min per 3.4.4.4.(1). An additional vestibule is not required per 3.3.5.4.(1) as it is not a storage garage, it is a repair garage.

These are virtually the same building. Scenario 1 requires a 2 h exit separation at the first storey (Part 9), and Scenario 2 requires a 45 min exit separation at the first storey (Part 3). How curious. 


Integrity of Exits (3.4.4.4.)

This requires a lot of coordination, and I have found it is not well understood (for how I interpret the Code anyways).

On top of fire separation requirements in Section 3.1., an exit fire separation has additional restrictions to ensure service penetrations do not adversely affect the integrity of the exit. This means, that what may be okay for a typical fire separation, is not good enough for an exit fire separation. These additional requirements are found in Article 3.4.4.4., and apply to the exit stair, as well as any exit corridor which connects an exit stair to the exterior.

Sentence 3.4.4.4.(1) states:

You will notice that ductwork is not a permitted penetration in an exit separation. Even if the duct has a fire and/or smoke damper, it is not permitted by Code. There is a reference in Part 6 in regards to ducts in exits, however I assume this is an oversight. If you have thoughts on ducts in exits, please share them in the Community Q & A here. Yes – I posted the question myself. And, no – no one has answered. Don’t leave me hanging!

How I read the above is that if something is not listed in (a) through (e), it better not be penetrating the exit separation. It seems straightforward to read, but I have found applying this to be a nightmare.

Something to note is that I have not spend much time in the field, and most of my Code work has been on the plan review side. So, it took me a while to realize that exit walls are penetrated all the time, as partial penetrations. See the image below for what I mean by a partial penetration. Essentially, the outer membrane of the exit fire separation is penetrated, but not the inner membrane.

If I’m to read the Code and apply it how I believe it was intended, partial penetrations would not be permitted. A fire separation is a system, and to me the outer membrane is a part of that system and is also required to follow Sentence 3.4.4.4.(1). I understand that it is easier during construction to allow partial penetrations, but it seems to me like this is a design and a habit issue, as opposed to a Code issue.

If I had any confidence that walls did not end up looking like swiss cheese over time and penetrations were always fire-stopped appropriately I might not be as concerned…but I have a few too many Fire Inspector friends who deal with buildings long after the initial work is done to be okay with the status quo.

From my experience, it depends on the AHJ how partial penetrations are interpreted and enforced. When interpretation is an issue, I highly recommend check with the AHJ early on as it can affect system designs.

There is a BC Building Code Interpretation that seems to address partial penetrations and notes that they are okay in the outer membrane. A reminder that interpretations are not legally binding and an AHJ may still disagree with them. There is also a Community Q & A regarding partial penetrations which could use your insight!


Exits Through Lobbies (3.4.4.2.)

The only slight relaxation for exit requirements is when an exit is permitted to lead through a lobby… which I have seen applied very loosely in many instances.

The word ‘lobby’ is where I think most of the confusion stems from. The lobby still needs to provide a high level of protection, and should not contain an occupancy. There are actually only a few relaxations permitted, which are:

  • Spaces other than residential, care, industrial, or service rooms can open onto the lobby,
  • The fire separation between the lobby and a room for direct supervision does not require a fire-resistance rating,
  • The fire separation between the lobby and adjacent occupancies does not require a fire-resistance rating if the building is sprinklered, and
  • Passenger elevators can open onto the lobby.

You will also notice that ductwork is not a relaxation for an exit though lobbies, however I am often told that it is ‘standard practice and acceptable’. If the Code did permit duct penetrations, I would imagine the Code would also require smoke dampers at those locations, which it does not (see Sentence 3.1.8.7.(2))…. some food for thought. If you have some thoughts on this, please share them in the Community Q & A here. Yes – I am the only only who has shared thoughts…please join me in the discussion!

If you are super keen, check out the NRC Users Guide pages 84/85 for additional information. It’s quite interesting to read, as how we perceive lobbies today seem to greatly vary from the way the relaxation was initially intended.

You can also check out the CFSA Newsletter (Page 15) which discusses Toronto’s approach to lobbies containing combustible materials.


Continuity of Fire Separations (3.1.8.3.)

If you like solving Code riddles, this one is tons of fun! Sentence 3.1.8.3.(3) has requirements for exit enclosure shafts and states:

Because of how it is worded with ‘shaft penetrating a roof assembly’ listed first, most people don’t read on and see that this is also applicable to exit enclosures.

I find this comes into play often when you have exit corridors, or an exit stair that is at the center of the building and has a horizontal extension to the outside of the building. This also applies when there is an attic space above the exit shaft. How I read the Code is that in either scenario, the vertical walls of the exit (enclosure/corridor or shaft) are required to be carried up to the underside of the floor or roof. I have run into countless designs where there is a service space above that has not considered this requirement.



As you can tell, I love exits and am a self proclaimed advocate for them. It’s easy to argue or interpret things a certain way if you are solely on the design and construction side and get to walk away from a building once occupancy is given. If something is easier and you can justify it in the wording of the Code, then may seem like the right path.

The truth is, that the design and construction period is a teeny tiny part of the life of a building. And as they say, “an ounce of prevention is worth a pound of cure”. If you don’t have a background in the fire service, I encourage you to share this article with someone who does and get their thoughts. There is a massive chasm in our industry between design and operation…and you have the power to help bridge it by considering how others could be impacted by the choices you make on the design side.

Want to Dive Deeper?

Get a FREE downloadable guide summarizing 7 Things to Remember During Design of Exits here. On the Resources page, scroll down and you will find the guide!

I also cover exits in the Kilo Lima Code School Building Codes: Part 3 Fundamentals course…come learn with me!


If you enjoyed this post, we encourage you to share!

Leave a Reply

Your email address will not be published. Required fields are marked *

About the Author
Recent Posts